Single-phase transformers vertically mounted with composite core

Katalogový list

315 – 17 000 VA

Provedení: JVT, JVR, JVD

SKU: 9A Categories: ,

Description

Single-phase transformers with standard UI shape lamination with composite core are intended for vertical mounting. They are produced in accordance with ČSN EN 61 558 in any voltage transfer combination between 1 V and 1 000 V, frequency 50/60 Hz, protection IP00, terminals IP20, insulation class B and a maximum ambi-ent temperature of 40°C. Their sizes and rated outputs are shown in the table. The transformer can be housed in an IP23 steel case. Optional changes to the design include protective shielding, higher insulation class, higher ambient temperature, primary or secondary winding protection, or the addition of thermal fuses.

JVT – vertically mounted with transformer terminal blocks

JVR – vertically mounted with feed-through terminal blocks

JVD – vertically mounted with stud terminals on insulating plate

Type Design Dimension
[mm]
Rated output [VA] Weight
[kg]
A B1 B2* C1 C2 D E F
U3232 JVT, JVR, JVD 127 100 150 175 200 80 56 7 × 10 315 5,1
U3240 JVT, JVR, JVD 127 110 160 175 200 80 64 7 × 10 500 5,9
U3250 JVT, JVR, JVD 127 120 170 175 200 80 74 7 × 10 630 7,1
U4060 JVT, JVR, JVD 158 140 190 212 250 100 90 7 × 10 1 200 14,0
U4066 JVT, JVR, JVD 158 145 195 212 250 100 96 7 × 10 1 600 15,6
U5052 JVT, JVR, JVD 200 135 190 250 286 124 93 9 × 18 2 000 21,0
U5065 JVT, JVR, JVD 200 148 205 250 286 124 106 9 × 18 2 500 25,0
U5077 JVT, JVR, JVD 200 160 215 250 286 124 117 9 × 18 3 150 30,0
U6063 JVT, JVR, JVD 237 155 210 306 345 124 122 9 × 18 4 000 38,0
U6078 JVT, JVR, JVD 237 170 220 306 345 124 137 9 × 18 5 000 43,0
U6093 JVT, JVR, JVD 237 185 235 306 345 124 152 9 × 18 6 000 50,0
U7073 JVT, JVR, JVD 280 175 205 385 410 176 150 13 × 20 7 500 60,0
U7088 JVT, JVR, JVD 280 190 220 385 410 176 165 13 × 20 8 300 66,0
U70103 JVT, JVR, JVD 280 205 235 385 410 176 180 13 × 20 10 000 76,0
U8083 JVT, JVR, JVD 315 195 225 437 445 196 160 13 × 20 11 500 85,0
U80110 JVT, JVR, JVD 315 225 250 437 445 196 190 13 × 20 14 000 105,0
U80140 JVT, JVR, JVD 315 255 280 437 445 196 220 13 × 20 17 000 127,0

This dimension is indicative only; terminal block sizes depend on the rated current.