Description
Single-phase safety isolating transformers are designed for supplying equipment in rooms for medical purposes. They are manufactured according to EN 61 558-2-15 with voltage transfer 230 V / 230 V, frequency 50 / 60 Hz, protection IP00, terminals IP20, insulation class F (155 °C), maximum ambient temperature 40 °C. Other voltage transfers are also possible, for example 400 V / 230 V. Transformers have reinforced insulation and shielding between primary and secondary windings, no-load current I0 < 3%, short-circuit voltage uk < 3%, voltage drop (regulation) ∆U < 5%, inrush current max. 8 times rated current (peak/peak). The transformers are equipped with a Pt100 temperature sensor. It can also be manufactured with the UP62 thermal expansion sensor (250 V / 2.5 A) upon agreement with the sales department.
Our range of single-phase safety isolating transformers for power supply in medical rooms is tested and certified according to EN 61558-2-15. Testing and certification was carried out by the Electrotechnical Testing Institute in Prague.
The certificate can be found here.
STD-line with Pt100 temperature sensor
Typy (230 V / 230 V) |
Rated output | Recommended protection
on the primary winding |
Parameters | Weight [kg] |
|||
---|---|---|---|---|---|---|---|
[VA] | η [%] | uk [%] | ΔP0[W] | ΔP [W] | |||
JOC U50103–0234 | 2 500 | DII 16 A gG | 97,3 | 2,8 | 33 | 110 | 38 |
JOC U50103–0235* | 3 150 | DII 20 A gG | 97,1 | 2,6 | 35 | 131 | 41 |
JOC U6078–0063 | 4 000 | DII 25 A gG | 97,3 | 3,0 | 40 | 158 | 42 |
JOC U6093–0064 | 5 000 | DII 35 / 50 A gG | 97,6 | 2,9 | 50 | 225 | 52 |
JOC U7073–0209* | 6 300 | DII 50 A gG | 97,2 | 3,0 | 60 | 270 | 61 |
JOC U7088–0025 | 8 000 | DII 50 A gG | 97,3 | 2,8 | 70 | 290 | 70 |
JOC U70103–0100 | 10 000 | DII 63 A gG | 97,3 | 2,5 | 80 | 320 | 90 |
* in stock
Technical parameters ECO-line with Pt100 temperature sensor
Type | Dimension [mm] |
Terminal [mm2] |
|||||
---|---|---|---|---|---|---|---|
A | B1 | C | D | E | F | ||
U50103 | 200 | 190 | 250 | 124 | 145 | 9 × 18 | 16 |
U6078 | 245 | 220 | 310 | 124 | 137 | 9 × 18 | 16 |
U6093 | 245 | 235 | 310 | 124 | 152 | 9 × 18 | 16 |
U7073 | 280 | 235 | 385 | 176 | 145 | 13 × 20 | 16 |
U7088 | 280 | 250 | 385 | 176 | 160 | 13 × 20 | 16 |
U70103 | 280 | 265 | 385 | 176 | 175 | 13 × 20 | 35 |
* Terminal block for Pt100 2.5 mm2 connection.
The transformers can be placed in a steel enclosure with IP23 protection.
Kryty IP23
Type of transformer Artical number of case |
Bushings | Dimension [mm] |
Weight
[kg] |
|||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | F | G | H | I | J | |||
U50103 PLE 11111 – 0067 |
M20 × 1,5 | 300 | 400 | 392 | 124 | 362 | pr. 11 | 100 | 143 | 325 | 525 | 12,2 |
U6078 PLE 11111 – 0074 |
M20 × 1,5 | 360 | 385 | 439 | 124 | 345 | pr. 11 | 120 | 117 | 385 | 525 | 15,5 |
U6093 PLE 11111 – 0074 |
M20 × 1,5 | 360 | 400 | 439 | 124 | 360 | pr. 11 | 120 | 132 | 385 | 525 | 15,9 |
U7073 PLE 11111 – 0058 |
M20 × 1,5 | 420 | 440 | 490 | 176 | 400 | pr. 11 | 140 | 114 | 445 | 581 | 16,9 |
U7088 PLE 11111 – 0058 |
M20 × 1,5 | 420 | 455 | 490 | 176 | 415 | pr. 11 | 140 | 129 | 445 | 581 | 17,3 |
U70103 PLE 11111 – 0057 |
M20 × 1,5 | 420 | 470 | 490 | 176 | 430 | pr. 11 | 140 | 144 | 445 | 581 | 17,7 |