Single-phase safety isolating transformers for power supply in rooms for medical purposes ECO- line reduced loss series

Katalogový list

2,5 – 10 kVA

Provedení:  Pt100, (UP62)

SKU: 11B Categories: ,

Description

Single-phase safety isolating transformers are designed for supplying equipment in rooms for medical purposes. They are manufactured according to EN 61 558-2-15 with voltage transfer 230 V / 230 V, frequency 50 / 60 Hz, protection IP00, terminals IP20, insulation class F (155 °C), maximum ambient temperature 40 °C. Other voltage transfers are also possible, for example 400 V / 230 V. Transformers have reinforced insulation and shielding between primary and secondary windings, no-load current I0 < 3%, short-circuit voltage uk < 3%, voltage drop (regulation) ∆U < 5%, inrush current max. 8 times rated current (peak/peak). The transformers are equipped with a Pt100 temperature sensor. It can also be manufactured with the UP62 thermal expansion sensor (250 V / 2.5 A) upon agreement with the sales department.

Our range of single-phase safety isolating transformers for power supply in medical rooms is tested and certified according to EN 61558-2-15. Testing and certification was carried out by the Electrotechnical Testing Institute in Prague.
The certificate can be found here.

ECO-line (reduced losses) with Pt100 temperature sensor

Type (230 V / 230 V)
Rated Output Recommended protection

on the primary winding

Parameters Weight

[kg]
[VA]  η [%] uk [%] ΔP0[W] ΔP [W]
JOC U6063–0068 2 500 DII 20 A gG 97,3 2,3 11 70 40
JOC U6063–0067* 3 150 DII 25 A gG 97,1 2,3 14 95 40
JOC U6078–0078* 4 000 DII 32 A gG 97,3 2,1 16 110 45
JOC U6093–0080* 5 000 DII 40 A gG 97,6 2,0 20 125 50
JOC U7073–0226* 6 300 DII 50 A gG 97,2 2,2 22 180 53
JOC U7088–0037 8 000 DII 50 A gG 97,3 2,2 25 220 67
JOC U70103–0108 10 000 DII 63 A gG 97,3 2,2 30 280 75

* in stock

Technical parameters ECO-line with Pt100 temperature sensor

Type Dimension
[mm]
Terminals
[mm2]
A B C D E F
U6063 244 155 405 124 125 9 16
U6078 244 170 405 124 140 9 16
U6093 244 185 405 124 155 9 16
U7073 284 175 456 176 125 11 16
U7088 284 190 456 176 140 11 16
U70103 284 205 456 176 155 11 35

* Terminal block for Pt100 2.5 mm2 connection.
The transformers can be placed in a steel enclosure with IP23 protection.

IP23 covers for ECO-line transformers

Type of transformer
Articel number of case
Bushings Dimension
[mm]
Weight

[kg]

A B C D E I J V
U6063
PLE 11111 – 0105
M25 × 1,5 360 370 487 124 330 385 315 325 13,2
U6078
PLE 11111 – 0105
M25 × 1,5 360 385 487 124 345 385 330 385 13,2
U6093
PLE 11111 – 0105
M25 ×1,5 360 400 487 124 360 385 345 385 13,5
U7073
PLE 11111 – 0084
M25 ×1,5 420 440 533 176 400 445 385 445 18,0
U7088
PLE 11111 – 0084
M25 ×1,5 420 455 533 176 415 445 400 445 18,2
U70103
PLE 11111 – 0117